Ron B asked ... How can I adjust my 2024 Honda Jazz Crossover?    |    vic asked ... How do l get my vauxhall combo radio to work with MP3?    |    Cass asked ... Replacing full bulb housing unit in Neff oven?    |    Pádraig O Sabhain asked ... How to fix Kenwood Slimline Dishwasher KDW45X20 with a F1 Er?    |    keith asked ... How to reset after battery change?    |    Click here to ask your question

boiler keeps going till it steams up?

hi all, puma 100e~keeps needing a top up of water# turn heating on and it keeps burning until it steams up and locks out but not heating any of the pipes, also hot water works if you reset but the when you turn water off it bubbles and gurgles and steams up again then locks itself out

any ideas cheers all
nick w, March 2010
You seem to be describing multipule faults there.

"keeps needing a top up of water"

Check all radiator valves, under boiler for leaks etc, check copper pipe outside (see if it has been dicharging water. If it has look towards Presssure Relief Valve or Expansion Vessel)



"turn heating on and it keeps burning until it steams up and locks out but not heating any of the pipes"

Is the pump running? Sounds like a pump problem



"hot water works if you reset but the when you turn water off it bubbles and gurgles and steams up again then locks itself out"

This may also be a pump problem however if it it working...Behind the PCB there is a round brass housing (diaphragm) and coming out of the side there is a hexagonal brass tube with a spring and pin located inside this. Get someone to open the hot tap a few times to see if this pin is moving freely. If it isnt moving the diapgram may be faulty. If it is opening then not closing quick enough when you close the hot tap try putting some silicone grease in the spring area. (WD40 is an OKish alternative)

Paul, March 2010