3 hours ago Karen asked ... Royal 480nt cash register?    |    andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    Click here to ask your question

How can I fix My Boiler Glow-worm fuelsaver 55f?

My boiler does not fire up.the ignitor just sparks all the time... but when i loosen the (casing - front) the boiler lights no problem. It is not working correctly. How do I fix it??
Stig_, June 2004
have you checked the ignition lead ,it may be sparkin against the caseing ,or there may be a prob with the pressure switch,to check pressure switch suck on the red tube connected to it if boiler lights just change the switch.

martin, April 2005
How can I change the fan of my boiler. My boiler is a Glow-Worm combi (Swift flow). Thank you.

B. Diallo, December 2004
If you take out the fan, just inside the outlet pipe of the fan unit are a set of like baffles, they are only held in with one or two screws, anyway, take them out, wash with soap and water, replace and fire up!

Matt Disney

Matt Disney, July 2004
It sounds like the flue is not letting in air, maybe It's blocked.

BigA, June 2004
link Click here to see other fixes for Glow-worm 55f.