narnia asked ... Matsui ct-111ss?    |    Jason asked ... How to fix handset problems ( intercom ) and access control?    |    andy asked ... Samsung VP-D60 camcorder?    |    Shopper asked ... Poor Renault Radio Reception?    |    reg bardle asked ... Lg 7kg dd?    |    Click here to ask your question

vokera excell 80 sp PROBLEM?

heating fine , but wene i run hotwater it goes to full burner and shortly it goes to low burner thus colder water , engineer has swapped thermister/ modulator/ diaphram, and now thinks its the pcb!! , can you help , hes mentioned gas presssure fine on heating but fluxuates on water side . regards andy
andy galbraith, December 2007
yes its going to low flame , im planning to clean up exchanger and venturi pipes tomorrow , any tips ?

andy galbraith, January 2008
It doesn't take long to remove the domestic heat exchanger, this may be blocked.

Big A, December 2007
Are you sure it is modulating down to low burner and not cutting off and going to pilot?. Does the flame go down with a click from the gas valve?.

c, December 2007
link Click here to see other fixes for Vokera.