how can i get my oil burner to run?

being new to my oil boiler,a Grant euroflame 50/70 i unfortunatly let the existing oil run out. its now been filled but it just wont work, the lockout light is on. when i reset it the motor runs but then cuts out after a few seconds, time and time again. it was working perfect before it ran out. please help, im freezing
paul, February 2008
hi to bleed the oil burner which pipe is it would it be were the two pipes meet ?

marie, January 2009
You need to bleed the oil feed line from the tank first - this involves removing the supply pipe connection to the pump and allowing the oil to run bubble free before reconnecting again. Once this is done, the pump itself will have a bleed valve somewhere, and you can let any remaining air out once the burner is running.

John, February 2008