58 mins ago Alan asked ... Problem with JCB 3CX transmission?    |    Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Click here to ask your question

Ferroli 102 DHW intermittent?

My 102 is about 7yrs old. Long been a problem with DHW cycling between hot and cold a nuisance in the shower. Thermistors have been changed, PCB as been changed. Now the boiler will shut down when providing DHW, sometimes requires a reset, sometimes will come OK after time. The whole thing appears to be unpredictable. My service firm have made 7-8 visits in the last month and dont seem to understand the problem.
arbee., February 2008
If the problem only happens with hot water, it is probably the flue fan venturi either cracked or brittle, or the fan impellor is dirty causing insufficient air flow to operate the air pressure switch.

DC, February 2008