Steve asked ... Gilera runner 180 vxr 2001 ignition replacement?    |    Janboy68 asked ... How can I mend my KitchenAid Artisan toaster?    |    rick asked ... How can I fix my portable Zenith DVP615 DVD player? When I p?    |    Jim asked ... How can I get my scarifier to work?    |    george crawford asked ... Citroen C3 Picasso?    |    Click here to ask your question

mcb trips out?

just fitted a trident 9.5kw shower after 5 mins mcb trips out and mcb is very hot can u help please
mr french, March 2008
When I first installed electric showers some 25 years ago the typical rating would have been in the region of 6-7 Kw. These days it's more likely that the rating is 9Kw +. If you have installed your new shower using and existing circuit it is very likely that the cable is underrated. It seems to me that you are exceeding the current of the circuit which is very dangerous as overloaded electrical circuits cause fires! Please get your electrical system checked out by a qualified electrician before it's too late.

MikeW

MikeW, March 2008
Shower also needs to be protected by a separate 30 mA/40A RCBO or else a 30 mA RCD with the 40A mcb.

J, March 2008
your cable is more likely under sized as well

andy, March 2008
The mcb needs to be of a current rating suitable for your shower, which will take 38 amps at 250v. The nearest size is therefore 40 amp.

John, March 2008