andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

rsf84e loss of water ?

fires up in morning preasure goes past 3 bar burner does not cut out ,so starts leting water out of safty valve.
mark, April 2008
IN MORNING PREASURE IS ON 0 BAR I TOP IT UP TO 1 BAR ,20 MINUTES LATER IT GOES PAST 3 BAR BURNER DOES NOT GO OUT THEN WATER STARTS COMMING OUT OF RELIEF VALVE.RUNS OK MOST OF DAY ,IN MORNING SAME AGAIN.

MARK, April 2008
I have an RSF84E(T) and it is a sealed system which is topped up from a mains water loop which should normally be closed. If there is water coming from the safety overflow everytime it starts up it must be being replaced from somewhere? Check the mains water loop is closed. I run my system at 1 Bar only.

Allen F., April 2008