Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Click here to ask your question

how to replace pressure relief valve worcester 24i combi boiler?

When turning on central heating the system pressure increases to maximum. I think the pressure relief valve is not operating correctly and wish to replace this. I know the system must be drained and replacement appears straightforward, but I should appreciate advice on any problems which may exist.
james lloyd-kitchen, April 2008
if when the heating is turned on the guage rises from say 1.5 bar when cold to 3 bar plus when hot then its the expansion vessel at fault. it could be flat but more than likely its knackered.

the pressure release valve is a valve that opens up when the system pressure gets too high. its a safety device and if it allows water out the relief pipe when the system pressure gets high and not when cold then the valve is fine.

iain, April 2008
link Click here to see other fixes for Worcester 24i.