Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

Low water pressure indicator Ariston Eurocombi?

I have an Ariston Eurocombi boiler (A/23 MFFI) which has decided to stop working. The 'low water pressure' indicator has lit up- but the gage shows 1.5 bar - which should be perfect. I've taken it right up to 2.5 bar, then drained the system down to nearly zero, then back up to 1.5 in a bid to try and reset it - but still this indicator remains lit with no other sign of life from the boiler. Have also switched it on & off from the mains - no joy. Every time i turn it on, it remains completely silent for 1 minute and then stubbornly lights up the 'low water pressure' indicator. Any suggestions anyone?
Malcolm McKay, April 2008
Thanks T, yup definitely the pump which i've now managed to replace.
Many thanks!

Malcolm McKay, April 2008
may be a pump problem, does the pump run?
do you see a 'slight' increase (then decrease) in water pressure as the pump kicks in?

I dont have a manual here for this boiler, so unsure if it uses a pressure switch or a flow switch, but either should be checked for continuity once the pump has been comfirmed to be working.

T, April 2008