andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

my boiler pressure has dropped to 0.4 and is flashing = no heating?

i turned off the heating and hot water for 2 days as i was going away. came back an dthe heating isnt working and the boiler is flashing 0.4 at the bar. how do i get the pressure up to get the heating to work?
desperate for central heating, April 2008
You need to find the filling loop - thats the valve that allows fresh water from the main into your boiler, increasing the pressure. Open the tap on the loop, and watch the pressure rise. You don't say what make of boiler you have - some filling loops are a flexible steel braided pipe with a tap on - some newer boilers have a plastic tap inside the casing.

John, April 2008