narnia asked ... Matsui ct-111ss?    |    Jason asked ... How to fix handset problems ( intercom ) and access control?    |    andy asked ... Samsung VP-D60 camcorder?    |    Shopper asked ... Poor Renault Radio Reception?    |    reg bardle asked ... Lg 7kg dd?    |    Click here to ask your question

10kw cooker 32amp circuit - clarification please?

As detailed earlier my cooker is 10kw total load as I would not be using all the features at the same time would I be ok to install on my 32amp circuit with 6mm wire
strawbs, April 2008
Your cooker could draw a maximum of 40 amps on full load - I'd go for a 50 amp breaker and 10mm wire - irrespective of how you intend to use the cooker. Look up IEE wiring regulations BS7671:2008.

John, April 2008