katlego asked ... Rev count on my 1982?    |    andrew asked ... "SECURE" on a yellow backround, and I cant ge?    |    Melodie asked ... How do I remove and change the basket? Duratech Identity Gu?    |    Kathy asked ... Samsung ER-4915?    |    Mark asked ... Oven door removal?    |    Click here to ask your question

10kw cooker 32amp circuit - clarification please?

As detailed earlier my cooker is 10kw total load as I would not be using all the features at the same time would I be ok to install on my 32amp circuit with 6mm wire
strawbs, April 2008
Your cooker could draw a maximum of 40 amps on full load - I'd go for a 50 amp breaker and 10mm wire - irrespective of how you intend to use the cooker. Look up IEE wiring regulations BS7671:2008.

John, April 2008