4 hours ago Alan asked ... Problem with JCB 3CX transmission?    |    Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Click here to ask your question

how do you drop system/boiler pressure on a Baxi 105e combi boiler?

I need to check the pressue in the expansion tank, and re-pressurise it if needed. When the central heating is switched on after about 10 mins the boiler pressure goes over 3 bar.
pete, April 2008
turn off boiler (at 3amp spur) turn both flow and return pipe isolating valves (beneath the boiler) to the off position.
Drain all water from the boiler via the drain cock (behind the pump) then test and recharge your expansion vessel as required.

When refilling the boiler, make sure to bleed the pump and ony run the pump (keep switching the boiler off before it fires) until the sloshing water noise abaits (ie all the air os out of the boiler) before firing

remeber to top up your system water back to 1-1.5 bar after you refill the boiler and bleed of the uppermost rads in the house.

T, April 2008