GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

Pressure in Worcester 35di boiler?

The pressure for my boiler drops very quickly. after filling the pressure to about 1.5 it drops to to zero in about 6 hours. do i need to replace the pressure relief valve?
prav, May 2008
Whatever is causing water to be lost from the system is the problem, not necessarily the PRV.
Check the expansion vessel has not lost its gas charge, or has its diaphragm perforated. It should take several seconds with the filling tap open to recharge the system to 1.5bar (maybe about 10s). If it "recharges" very quickly this is an indication of expansion vessel failure, as is a large change in system pressure from cold to hot. If it goes over 3 bar the PRV is designed to "drip".
Look for underfloor leaks too.

Phil J, May 2008
link Click here to see other fixes for Worcester.