Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Click here to ask your question

Pressure in Worcester 35di boiler?

The pressure for my boiler drops very quickly. after filling the pressure to about 1.5 it drops to to zero in about 6 hours. do i need to replace the pressure relief valve?
prav, May 2008
Whatever is causing water to be lost from the system is the problem, not necessarily the PRV.
Check the expansion vessel has not lost its gas charge, or has its diaphragm perforated. It should take several seconds with the filling tap open to recharge the system to 1.5bar (maybe about 10s). If it "recharges" very quickly this is an indication of expansion vessel failure, as is a large change in system pressure from cold to hot. If it goes over 3 bar the PRV is designed to "drip".
Look for underfloor leaks too.

Phil J, May 2008