4 hours ago Alan asked ... Problem with JCB 3CX transmission?    |    Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Click here to ask your question

over pressure baxi 105e?

pressure valve lets go at 3 bar .loop disconected .but water is passing through to heating system and running out of by pass
paul laff, May 2008
Sounds like Diverter valve diaphram valve.
Passing between c/h and h/w supply.?
the 2 mixing. giving presure.
got to be the diverter valve.

Neil.Plumbing, May 2008
Could be domestic heat exchanger. If pinholed inside would pass mains to central heating.

Kevez, May 2008