andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

CENTRAL HEATING TANK IN LOFT OVERFILLING WHY?

I FIITED A NEW BALLCOCK IN TANK BUT THE TANK IS STILL FILLING TO OVERFLOW CAN THE TANK BACK FILL FROM THE SYSTEM ANYHOW? I THOUGHT WATER ONLY CAME IN TO TANK FROM SUPPLY
STEWART, May 2008
could be the cold feed into the house crossing over in the back of a mixer tap and pussing up through the system and into the water tank, you havent stated which tank.

Baz, June 2008
water can backfill on both tanks.

f/e can backfill from a split coil in cylinder.
cws tank can backfill from the cylinder caused by cold mains entering into hot gravity.

what tank is backfilling need more info.

hi-spec plumbing & heating, May 2008
its a feed and expansion tank so yes it will rise when heating on for example. you may have the float set too high so it overflows when expansion occurs

iain, May 2008