andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

Ravenheat Boiler?

I have a Ravenheat RSF84ET boiler which gives out hot water when the central heating is on but when the heating is of it will only warm up for about 10 seconds and then go cold how can i solve this problem
Lee Plummer, June 2008
This was the thermistor on ours - replaced that, everything was fine. It was about £50 installed.

Dave Smith, July 2008
sounds like a problem with the dhw heat exchanger, it maybe scaled up or partially blocked.

other things to check it the dhw thermister & dhw flow sensor

T, June 2008