andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

BAXI COMBINATION BOIER?

BAXI COMBINATION BOIER

Power on
Presser gauge shows 2.5
CH and DHW mode
Boiler star going
Pump start
Fan does not come on.
I checked fan Terminals, there is no power there, when demand is on.
I checked the micro switched for DHW and CH both makes the connection, but fan doesn’t come on.
I manually make the Micro switches still fan does not come on.
Can you help please?
David. email; daraemami@yahoo.com, July 2008
Possibility- Look for a manual reset button on boiler- P.S. 2.5bar is too much and could possibly cause problems in the future. drop it down to about 1.5bar by letting a bit of water out of the rads.

Elvis, July 2008
firtly the water pressure is too high (should be 1-1.5 bar when cold) bleed excess from a radiator (do not use the safety valve!)

you said you checked the micro-switches, and say they make, assume you also checked the switch with a mutlimeter to ensure they are working too, and checked the voltages reach the pcb terminals...

would be suspecting a pcb fault if all checks out

T, July 2008