Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    tom schwartz asked ... Bosch maxx 6?    |    Noman asked ... Reverse light switch?    |    Suzie asked ... Stuck Feed dog?    |    Click here to ask your question

how can i fix my vokera combi boiler????

i have a vokera linea 24 model and i dont seem to have any pressure in my boiler what so ever, i have tried the valve underneath the boiler but that does not seem to be working either, its not putting the pressure back into the boiler for me and im almost down to the zero on the gauge.
Do you have any ideas what could be causing this please???
Tracey Marshall, August 2008
When operating the filler valve can you hear any water flowing into the system. If you cant then it could just be a faulty filler valve.
If you can hear water check if it is coming straight out of the pressure relief. A pipe comes from a valve under the boiler and will go out through the wall. This is there to let off pressure if it gets too high. Sometimes these will go faulty and contantly let pressure release from the system. If this is the case you will need to replace or call someone in to replace it.
If neither of these is the cure you may have a serious leak somewhere on the heating system pipework.

Robin S, September 2008