GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

how to replace diaphram on a compact 80e?

It has been leaking for some time now and for the last month or so the boiler keeps cutting off when you run the hot water. When the heating is on there is no problem at all. The diaphram cover is corroded and if you take the microswitch off you can visibly see water slowly leaking out. I cleaned out the microswitch with wd40 put it back on and it now works fine so the problem must be here. I have found the diaphram and cover assembly for £30 delivered. How do i stop the water from going everywhere when i take the cover off, and is there anything i need to know when changing this .Many thanks Gareth
Gareth Williams, August 2008
the valve mechanism in the diaphragm is crimped in place so, unless you've got access to specialised equipment, you'll have to replace the diverter valve itself. Its not a lot more expensive than the cover assembly. I managed to replace the diaphragm rubber at work and its lasted 5 years but now, once again, I'm replacing it.

Josh Hooker, August 2008