Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Click here to ask your question

Increase pressure in Ideal C95FF combi boiler?

We recently disconnected a radiotor before decorating, but once it was reconnected and the valves opened again the pressure indicator on the boiler dropped to 0 psi and now there is no heating operational. Hot water works fine. How do you add pressure to the heating system with this boiler?
Gareth, September 2008
from TOTAL BUILD AND HEATING do you have A filling loop on boiler if so just open and fill to 1.5 bar plus make sure all rads i.e vants are open to let air out 1 at a time plus keep toping up boiler when doing this untill you have 1.5 bar MINT HAY

JUSTTO GOOD ANDY 20 EXP, September 2008