Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Click here to ask your question

baxi combi boiler 105e high pressure problem?

this boiler is gaining pressure from 0.5 to 3 bar in about 24 hrs my expansion vessel was full of water so i thought this was the problem but i have changed it for a new replacement but the pressure problem is still their can any one advice
ian everard, October 2008
loseing pressure water leaking put up the pressure then by the next day the pressure has droped again the water leaking again

rav, February 2011
Firstly check filler loop is not passing water into system.(disconnect fill loop).if everything ok with fill loop.
Possible pinhole within plate heat exchanger

Grahame, October 2008