Alan asked ... Problem with JCB 3CX transmission?    |    Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Click here to ask your question

Baxi Cmbi Boiler 105e?

When cold pressure 1bar rises to 3bar when hot, in the morning no pressure, if cold and pressure at 1bar leave overnight there is no pressure drop.

Any advice.

Cheers
Taza, October 2008
if it rises when using your heating, its expansion vessel.

vessel has either lost its air charge or has split and air section is now full of water giving no free room for expansion.

vessel on back of boiler has tyre type valve, remove cap push pin in briefly:

if you get.....
air: maybe needs a bit more charge
nothing: needs charged
water: f*ck*d

iain, October 2008