Alan asked ... Problem with JCB 3CX transmission?    |    Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Click here to ask your question

How can i fix my sime friendly format 80E boiler?

When turning on the Central Heating and leaving it for approx. 30mins, the pressure keeps going over the blue zone onto 3 bars. I have bled all rads so no air in the system.

Can anyone please advise? Thanks.
Sohail, November 2008
sounds like the expansion vessel is broken , easy way to test it is to find valve on expansion vessel , its a small tyre valve on top of vessel . remove valve cap and depress pin in valve , if water comes out diaphragm in vessel has failed and vessel must be replaced . hope this helps

christian boiler man, November 2008