Jo asked ... How to engage clutch on old sewing machine to engage needle?    |    Jacky asked ... Miele Vacuum cleaner?    |    Ben asked ... Toyota Yaris French or Japanese?    |    Andy asked ... How can I mend my MacAlistair 450w hedge trimmer?    |    Felix asked ... Hitachi vt-m70em?    |    Click here to ask your question

How can i fix my sime friendly format 80E boiler?

When turning on the Central Heating and leaving it for approx. 30mins, the pressure keeps going over the blue zone onto 3 bars. I have bled all rads so no air in the system.

Can anyone please advise? Thanks.
Sohail, November 2008
sounds like the expansion vessel is broken , easy way to test it is to find valve on expansion vessel , its a small tyre valve on top of vessel . remove valve cap and depress pin in valve , if water comes out diaphragm in vessel has failed and vessel must be replaced . hope this helps

christian boiler man, November 2008
link Click here to see other fixes for Sime.