Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

Ravenheat gas boiler combi-pressure level?

Adjusted black marker to be level with red marker on 1 when boiler turned on for heating black marker moved to nearly 2 boiler turned off and blacker marker fallen back to 1.5. Should both black and red markers be at 1 when turned off?
John, November 2008
Red needle should be set to about a 0.5 so you know when to top up system.Black needle should sit between 1 and 1.5 when cold.When hot it may rise to as much as 2.5.This is ok.If it goes near 3 then you have a problem and will need a Corgi Engineer.

Gasman, November 2008