GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

how can i fix my glowworm compact 100 boiler?

i am having to fill my boiler each morning by means of a filling loop as the pressure has dropped during the day seems to be water coming out of the over flow pipe which comes from the boiler what is causing this
m brown, November 2008
You ned to replace the safety pressure release valve. I've gone thru 4 of tese on the same model boiler.

Once you turn that knob to release out pressure it never reseals again properly. It's a straight forward thing to change. One nut on the side and a clip on top. Isolate the boiler (ie switch everything off and close the pipes under the boiler) Remover the side nut. remove the clip then yank the valve out. It may need a good pull.

Replacement is just the opposite way around. But make sre your really push the new one home. If it starts leaking from the cip joint when you refill then give a good push on the valve to seat it properly.

Hope this helps

Steve, December 2008