1 hour ago Clare S asked ... Repair Electriq dehumidifier?    |    Bob asked ... Charger fault?    |    Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Click here to ask your question

Hot water on a Vailllant ecoMAX 828/2E?

The hot water from our Vaillant ecoMAX 828/2E takes a long time to get hot even when you have the water flow low. The bolier fires up fine and there are no error codes. The diagnostic codes are all OK. It seems that when the hot water is called for it partially goes into the heating system. Is there a valve that diverts the hot water to one or the other, or both as required? Any help would be much appreciated.
Tony Mower, March 2009
had fluctuating hot water, had heat exchanger flushed, now got lovely hot water and no heating, the boiler fires up when the heating is put on, but no lights come on, trying to phone engineer but think he,s away, any suggestions.

debbieleec, September 2009
yes there is a motorised valve in the boiler, and it is letting by, so you need a new valve or a valve service kit.

parsons building services, March 2009