Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

Riello burner needs reset to start?

Can the amount of time the Riello 40 F5 burner pumps the oil before ignition attempted be increased? We have an in ground oil tank which needs a while longer to get the oil to the pump. Because of this burner does not fire and the reset button needs to be pressed to start it. This only happens if air temp is not too cold and the burner is off for several hours. This way the oil has slowly gone done in the pipe.
david, March 2009
Fit a Non Return Valve in the Suction Line, with the Arrow on the Valve pointing towards the Burner, this way the oil should not fall back to the tank!

Boiler Repairman - Ipswich, April 2009