2 hours ago Andrew - C asked ... Stannah 400?    |    Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    Click here to ask your question

How do I fix Triton Opal shower (cuts off elec mains)?

After about 3 or 4 mins normal use the shower cuts off completely,(usually when you are well soaped up) and trips the breaker in the consumer unit.
If the shower is left alone for 5 mins then reset at the
consumer unit,another 3 mins normal use then BANG
again!!
I believe the shower unit is 10.5 kw,and also the culprit!
Paul, April 2009
Sounds like the mcb breaker is not correctly rated, for a 10kw shower you would be looking at least a 45 amp rating type b mcb. But before you go uprating it check the shower cable is also the correct size, it should be 10mm cross section area. Above all else get it all checked out by a part p approved electrician.

Phil Morley, April 2009