Mike asked ... Bosch WTA74200GB Vented Dryer?    |    Stuart G asked ... C3 Front Wiper control problem?    |    Clare S asked ... Repair Electriq dehumidifier?    |    Bob asked ... Charger fault?    |    Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Click here to ask your question

Problem with Ferolli Modena 102 Combi Boiler?

Hi,

I've got a Ferolli Modena 102 which has got water constantly coming from the overflow pipe. The pressure is sitting at around 3 and the filling loop is disconnected so it seems to be drawing water in from the mains. Could this just be the expansion vessel that needs replacing/recharging or is it more likely the exchanger is perforated? What pressure should the expansion vessel be recharged to?
Hopon, May 2009
your preasure should be sitting about 1 to 1.5 bar when cold. it could be the safety blow off that is running should tell you on the vessel what the recharge pressure is.

stew, May 2009