Cass asked ... Replacing full bulb housing unit in Neff oven?    |    Pádraig O Sabhain asked ... How to fix Kenwood Slimline Dishwasher KDW45X20 with a F1 Er?    |    keith asked ... How to reset after battery change?    |    Carol asked ... How to remove roller from lawnmower?    |    Ariana Orellana asked ... Code?    |    Click here to ask your question

Heatline s24 fan doesn't come on?

Hi I have a problem with my Heatline S24 boiler, The power is on but the fault on air preasure switch light is flashing. after reading the manual several times I have come to the conclusion that even if the switch is faulty the fan should be running when there is a demand for water, but it isn't going. so would the fan being broken give the same fault light?
Peter Johnson, June 2009
we are an approved agent for heatline , the problem that you have we are almost sure it is the pcb board , part no 3003200010

combi-doc 07956830204, June 2009
I don't know your boiler but the general theme is that the fan runs first and the air pressure switch detects the fan running and the integrity of the case seal - if the switch senses that it's all OK then the lighting up process begins.

No fan = no pressure switch = do not continue firing up.

Peccavi, June 2009
Thanks for the reply
I thought the fan was meant to run tho, I guessed the switch is simply a relay that clicks on when presure is applied to it so i tried manually bypassing it by joining the two wires through a fuse but this had no effect?

Peter Johnson, June 2009
I suspect you have a faulty air pressure switch. Blowing into the air pressure tubes may do the trick. Remember to connect them back the correct way.

j, June 2009