i have noted what you have said, capital boilers and removed the burner cover and bridged the foremost of the two switches at the upper right hand side turned on the tap and the boiler fired up. kept on trying it bingo every time. If i need to get another switch/sender unit any ideas where to get it front.
thanks for the info.
allen, June 2009
What is the presser at one bar ? if yes then its the flow swich in side the boiler, This has to be taken out and cleaned or re placed because it block, the flow swich works the boiler ONLY when water is at 1 bar
capitalboilers.co.uk, June 2009
yes it is the same, and it only flashes once a second
allen, June 2009
does it do the same thing when you put your heating on?
Is the red flashing once per second, or faster (about 4 x a second)?