Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Mike asked ... Bosch WTA74200GB Vented Dryer?    |    Stuart G asked ... C3 Front Wiper control problem?    |    Clare S asked ... Repair Electriq dehumidifier?    |    Click here to ask your question

potterton profile 50e?

The boiler will not start, the fan runs OK but will not following the flow chart supplied by potterton comes up with the answer the pressure switch needs changing, so I changed it still no luck, have checked the enclose seal and the pipes are not kinked. If I cheat and suck on one of the pipes it will start. Any ideas?
Frank Emery, August 2009
Hi,

My old Potterton 50e has started to make a grinding noise when in hot water and ch mode. There is also a bit of kettling happening when the boiler is switched off (both modes) It does not sound healthy! Weirdly enough it started to heat only two radiators upstairs when on hot water mode (Central Heating was turned off)
This I guess is not normal - can anyone help?

Cheers,

Si

Simon, August 2009
Thanks everybody for the help, John turned out correct the flue had what looked like dried nettle leaves in it, perhaps a bird trying to make a nest!
its never happened before and the boiler has been there for about 17 years.

Frank Emery, August 2009
if the switch and tubes are ok then the fan isn't producing enough draught to operate the switch, try cleaning the fan impellers.

Ian, August 2009
have you checked the tubes are both clear ?

hi-spec plumbing & heating (essex), August 2009
I'm only a simple OFTEC man, but if this happens to me the flue needs a clean out...its the air pressure differential that causes the air switch to shut things down.

John, August 2009