dave s asked ... Transmission not working?    |    Tom asked ... Replace rear right door upper right latch cable - high roof?    |    ian asked ... Vaillant timeswitch 150 analogue unit (clock stopped?    |    Art Cour asked ... How do I get engine cowling off to find gas leaking?    |    liz asked ... Changing a belt?    |    Click here to ask your question

how do i repressurise my sime super 80 boiler?

Sime super 80 boiler. No manual available.
I get hot water briefly in shower but no hot water elsewhere in the flat. the pressure guage on the front of the boiler is just above zero so i suspect the system pressure needs topping up. How is this done/
TOL, August 2009
The Sime is a superb boiler, I have one myself. Somewhere down the MAIN COLD WATER INPUT pipe there will be the filling loop. This should be an armoured pipe running between the COLD INPUT and the HEATING RETURN. depending on the variety of the filling loop you may need to either just turn a tap or you may need a screwdriver to open the valve. Becareful, watch the pressure guage as you don't want to achieve more than 1.5bar (max)

Some installers years ago did not install the armoured pipe. so you may find two regular bibcocks if so carry-out the same procedure but do it very gently. remember 1.5 = maximum when the system is cold.

Townteck, August 2009