Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Mike asked ... Bosch WTA74200GB Vented Dryer?    |    Stuart G asked ... C3 Front Wiper control problem?    |    Clare S asked ... Repair Electriq dehumidifier?    |    Click here to ask your question

worcester iol heatslave 15/19 ?

burner locks out 15 min from cold then press burner lock out button boiler runs for a few mins longer then locks out again but when the boiler cools and the burner lock out button is pressed the boiler re starts and goes through the same process
nigel, September 2009
thanks had the same thought some where in the grey matter & its due for a service soon
thanks again nigel


ps all thumbs its OIL

nigel, September 2009
Sounds like the good old Solenoid Coil, but before changing it it would be worth cleaning the oil filters, nozzle & photoresistor, But penny for a pound it'l be the coil

www.elanar.co.uk, September 2009