Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Mike asked ... Bosch WTA74200GB Vented Dryer?    |    Stuart G asked ... C3 Front Wiper control problem?    |    Clare S asked ... Repair Electriq dehumidifier?    |    Click here to ask your question

how to fix worcester-danesmoor oil boiler?

the extraction fan in the flue is permanantly on in my worcester-danesmoor15/19 oil fired boiler.any suggestions on how to remedy this?
nick., September 2009
thanks for that. that sounds like a more accurate description of whats happening.

nick., September 2009
You don't have an Extractor Fan on this Boiler, I think you are trying to say that the Burner is constantly running in Post Purge mode, this is controlled by a small Pcb in the Boiler Control panel, it has an electronic timer which runs the Burner fan for about 30 seconds when the boiler switches off. as your boiler has a LLD (low level discharge flue) the post purge was supposed to stop oily smells being blown back into the house after burner shut down, (it had limited sucess) You should be able to obtain a repalcement Post purge kit, from a specialist oil spares stockist
try Anglian Heating Components Ltd (01953) 607833

www.elanar.co.uk, September 2009