andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

boiler keeps cutting out?

Glowworm 30sxi. We had the water turned off to install new bathroom taps. Water was turned on and all seemed ok but after plumber left boiler started failing. First F5 but after resetting got hot water no rads. Then nothing. The pump's working but everythings running either cold or overheating if I turn the temp setting up.
Suzanrs, September 2009
Its possable that by draining the system you have got an air lock in the heat exchanger this can cause the boiler to lock out also check that the heating valves have been open`ed under the boiler

jts plumbing, September 2009
F5 is an overheat fault. Did the plumber drain the heating system? Just turning off the water supply should not cause this problem unless it was drained.

Ian, September 2009