4 hours ago Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    tom schwartz asked ... Bosch maxx 6?    |    Noman asked ... Reverse light switch?    |    Click here to ask your question

ARISTON micro Genus HE 24 MFFI Boiler showing E34? BOILER WILL NOT OPERATE?

showing E34?
BOILER WILL NOT OPERATE
JOHN, September 2009
I replaced the fan in my MicroGenus HE 24 with the more powerful one from the 28/32 and can confirm it works. Thanks thermoman for the tip!
Search for article number 65102566 (my manual was misprinted, check the Ariston site to confirm part numbers), the fan you're after is 80W instead of 47W

mrsliv, January 2011
Hi, this morning i've also had this error. i look at the flue restrictor but i founded none. I finally find out where the problem was. the condensate trap (where the condensate goes before it left the boiler) was full of limestone, so the condensate coulnd not be evacuate. I'd just to drain (there's a valve for) the trap. I hope my experiment can help.

firestarter (from belgium), December 2009
flue restrictor should be removed

netY, October 2009
or air pressure switch is knackered, bout £30 for new one, easy change -check manual.

naz, October 2009
Alternatively u could check all tubes running to and from switch, make sure not blocked, also check flu is clear.

naz, October 2009
Air pressure switch is not seeing fan, even thou fan may be running, fan down on efficiency, change fan- around £60 for new.

easy install, look in boiler manual.

Naz, October 2009
fan / air pressure switch fault. Get a qualified engineer to have a look.

Ian, September 2009