katlego asked ... Rev count on my 1982?    |    andrew asked ... "SECURE" on a yellow backround, and I cant ge?    |    Melodie asked ... How do I remove and change the basket? Duratech Identity Gu?    |    Kathy asked ... Samsung ER-4915?    |    Mark asked ... Oven door removal?    |    Click here to ask your question

about pressure on Baxi 80e gas boiler?

after overpressurising the system we operated the pressure relief valve and the pressure then reduced to required level of 1.5 but its not staying there - after turning back the pressure relief button fully we find the water continues leaking from the expansion pipe outside and only stops when empty and pressure below minimum level.
Bettee, September 2009
You have committed the cardinal sin - never reduce pressure via the prv as it won't seal afterwards. Much better to have a new one fitted now.

John, September 2009