andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

expansion vessel is full of water and the boiler is locked out ?

heatslave 15/19 is locked out and the expansion vessel is full of water i believe i need a new vessel but will this be the only problem?
les mclean, October 2009
Your Vessel needs recharging with compressed air to 1-00 Bar, keep a drain valve open whilst pumping up to allow the water to discharge from it, as long as the air charge holds at 1-00 bar, the vessel can be deemed as OK, (it should be recharged at every annual service)
The Lock-out problem is not connected with the expansion vessel, and should be investigated by an oil engineer, it does sound like this boiler has been poorly maintained.

www.elanar.co.uk, October 2009
Definitely you need a new expansion vessel. It should be filled to around 10 psi with air or nitrogen, and when its in place, increase your boiler pressure to around 1 bar.

John, October 2009