GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

worcester bosch 240 pressure on 3 bars?

does anybody no how to release the pressure to get it back down to 1.5
john, October 2009
Try to find the central heating drain point outside (below floor level on the outside wall, with a square head on the screw part), open that and let the pressure fall. If the pressure continues to rise, your filling loop is not properly closed, or (rarely) the dhw heat exchanger has a hole between the primary and secondary water and would need replaced.

Iain, October 2009
Bleed water off from the radiators - it takes a while, you may need to lose a couple of pints but its the most boiler friendly way!

John, October 2009