2 hours ago T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Mike asked ... Bosch WTA74200GB Vented Dryer?    |    Click here to ask your question

potterton neataheat 10-16 only works from cold?

ignites from cold heats up switchs of at temp
rads drop in warmth pump runs heater starts up
does not ignite have to switch off let get cold for
it to ignite again
phil, November 2009
If you have a fan that starts up before the boiler ignites , then there is also an AIR PRESSURE switch.

The problem may be due to a partially blocked plastic pipe between the switch & fan.

It goes via an inline metal restrictor ( inside the plastic tube) that can block up.

Remove the tube and suck/blow so that you can hear the Air Pressure Switch clicking...then replace the tube.

A very common Netaheat fault....on these boilers with the fan + pressure switch !

Beware scrapping the boiler as most parts are still available (Ebay etc) so don`t jump to any expensive conclusions.
(and don`t believe what the CH engineers or Gas Board tell you. These old boilers are built to last....more than 28 years if necessary!)