3 hours ago T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Mike asked ... Bosch WTA74200GB Vented Dryer?    |    Click here to ask your question

pressure?

Every time i have had the heating on why do i have to put the pressure up everytime i have turned it off
Mandy, November 2009
System pressure should be set cold at approx 1.2 - 1.5 bar on the guage. when heating is on, pressure will rise upto 1.8/2bar. If pressure reaches towards 3bar, water will discharge from the pipe outside to protect boiler. when it cools pressure will be down because water has been lost. If this is the case, expansion vessel is at fault

chris m - ravenheat specialist, November 2009