Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    tom schwartz asked ... Bosch maxx 6?    |    Click here to ask your question

glowworm/combiboiler/swiftflow?

looses water pressure when in stand-by. when you recharge the pressure and use it the system goes upto 2.5 bars pressure, then drops below 0.5. in stand-by
the minimum pressure should be 0.7 wich is what i charge it to.
jonathon@markwhite999.freeserve.co.uk, March 2006
have you got water coming out of the overflow outside??

if so the pressure release valve is stuck ope like mine was, had it replaced and it was fine, only cost about £10

Trigger, April 2006
Check the pressure in the expansion vessel using a tyre pressure guage when the system is under zero pressure. It should be about 0.8 bar. If not pump it up with a bicycle pump.

Gaz, March 2006