GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

low pressure ?

low pressure system light on my potterton puma is on no leaks bleed radiators pressure holds but will not fire up.
alan, November 2009
likely to be either and faulty low water pressure switch or the switch is blocked with sludge.

Brucey, November 2009
My husband and i have exactly the same problem today and looking on a post on here managed to get it working. All be it that we were petrified of blowing ourselves up!!!

Turn your boiler off at the mains (electric switch), but leave the pilot light on as well as the central heating switched to on.
You need to remove the front casing from the boiler. then locate the 2 yellow wires that go into the same white clip. Remove this clip.
Turn the mains back on. Your boiler should fire up immediately.
Leave for 1 - 2 mins. Then switch back off at the mains. Once this has been done. put the yellow wires clip back into the relevant place. We blew on our plug first incase of any dirt. Then turn mains back on. Voila should be back and running OUrs was. The replace all the coverings.

Hope this helps you

KFITZ090509, November 2009
link Click here to see other fixes for Potterton.