Bob asked ... Charger fault?    |    Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    Click here to ask your question

How to pressurise expansion vessel?

Vaillant Combi boiler VCW 282 central heating expansion vessel needs to be re pressurised as it is causing high pressure in operation causing pressure relief valve to operate giving rise to re- filling twice daily. How to check expansion vessel pressure and how to repressurise it What kind of air pump is required
and what kind of cheap pressure guage is required to check expansion vessel pressure
Donald Finlayson, December 2009
Many thanks for the information To both Dave M and a ''heating engineer''
Could Dave M please clarify first words ''Locate Sharadar Valve'' I am not familiar with the term Sharadar Valve Many thanks Donald Finlayson

Donald Finlayson, December 2009
locate sharadar valve [air side] usinng a car tyre foot pump preferabley with system no pressur on it [test for no water in air side apply a small screw driver into same mutch lick letting a car tyre down.pump up vessel to 1 bar or 14.2 lb/ sq ins. once re pressurised top up system and vent rads.

dave m, December 2009
all you need is a tyre press gauge & a bicycle pump, when press is zero pump vessel to 1/2bar(7-8 psi) then pressurise system from cold feed to 1bar. job done. but if you have water coming out of the air valve when you depress it, your expansion vessel is kaput & needs to be replaced. you MUST also put some more corrosion inhibitor in the system. No dont ask me, its too complicated for the layman.

a heating engineer, December 2009