narnia asked ... Matsui ct-111ss?    |    Jason asked ... How to fix handset problems ( intercom ) and access control?    |    andy asked ... Samsung VP-D60 camcorder?    |    Shopper asked ... Poor Renault Radio Reception?    |    reg bardle asked ... Lg 7kg dd?    |    Click here to ask your question

EXPANSION VESSEL - RE-PRESSUREIZE HOW?

I need to re-pressurize my expansion vessel ...
do I drain the heating circuit then pump up the vessel to 1bar then release the pressure via the valve then refill the system to 1bar with water in that order ??? Thankyou
Martin, January 2010
Thanks Ian, think I got ya. so once the air has been pumped into the expansion vessel that reading is on the foot/bicycle pump guage and bears no relation to the pressure guage on the front panel of the boiler - thats there purely for the water pressure ?

Martin, January 2010
the drain cock outside is best to use, usually at low level on outside wall, but any drain will do. so long as the pressure you are pumping in has somewhere to go otherwise you will get a false reading on the pressure gauge as you will be increasing the system pressure not the air pressure in the vessel.

Ian, January 2010
Thanks Ian, at the risk of sounding stupid, when u say 'open drain' do you mean drain all the rads and the entire heating system? OR the drain in the base of the boiler unit itself?? sorry .... thanks

Martin, January 2010
heating off, open drain, pump exp vessel to 1 bar, close drain, refill system to 1 - 1.5 bar, bleed pump & rads if req'd, top up pressure if req'd, heating on.

Ian, January 2010