Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    tom schwartz asked ... Bosch maxx 6?    |    Noman asked ... Reverse light switch?    |    Suzie asked ... Stuck Feed dog?    |    Click here to ask your question

How can i fix my dripping overflow pie on boiler?

What is causing a dripping overflow pipe
my boiler is a Vokera combi
A new heat exchanger fitted about a 18 months ago.
Nicholas Haar, February 2010
Water is getting past the overpressure valve, it may need replacing or more likely your pressure is going right up when the central heating is hot because your expansion vessel needs pumping up (and then the pressure release valve is letting by). Google it. If the pressure rises gradually with time turn off the water inlet tap, open a hot water bath tap to release any pressure and see if that stops the increase; if it does there is a path from the mains water to the radiator water loop, possibly via heat exchanger.

c, February 2010
link Click here to see other fixes for Vokera.