Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

how can i get my boiler fixed?

baxi 105E condensing boiler.3 years an old. losing pressure for 5 months now. adding water every day now as drops to red zone.no leaks found under floors except for one room (tiled and pipe under concrete )
One engineer told me to switch off boiler,put a bag on outflow pipe, increase pressure to 2 bar and watch!
Bag filled with water and pressure rose to just over 3 bar.Does this prove no leaks in pipe work?Been told system prob full of sludge (heat exchanger just changed as hot water kept fluctuating hot/cold) desperate now as £400 down and still not fixed.
Andrea, March 2010
top pressure up to 1.5 on pressure guage do this when system is cold to get a true reading switch on heating and watch guage if it goes up to 3 barr or over it could be one of three things ,expanssion vessel, filling loop letting by or plate heatexchanger if plate heatexchangers been changed that elimenates that try setting correct pressure again to 1.5 then if you can disconect filling loop and see if it leaks if not it will proberbly be the expanssion vessel if you like call me and il talk you through it 07923258885 between 9 and 4

john, March 2010