3 hours ago mike asked ... F+p 913t dishwasher?    |    Emma asked ... Foot pedal smoking?    |    Morne asked ... My defy dtl 125 toploader?    |    Ernie asked ... How to fix gearchange ldv maxus van 2006?    |    Cuckoo asked ... Changing batteries on a fixed bt corded phone?    |    Click here to ask your question

baxi combi 105 he?

pressure drops down when heating go off dripping from overflow pipe
brian, March 2010
Sounds as if your boiler is over expanding, either blockage to expansion vessel or not enough air in expansion vessel, check air first when boiler cold should be around 1 bar pressure can use a car tyre pressure guage or footpump to check. Red cyclinder usually housed at the very back of the boiler same type of valve as on car tyres

rawplumb, March 2010