Eed asked ... Brother KR850?    |    Lynne asked ... Disable Alarm Scantronic 9800?    |    Ron Minadeo asked ... Table won't close all the way?    |    Cam asked ... How can I fix my Bison 50 stairlift?    |    Alfred Briffa asked ... How to build a battery conversion adapter?    |    Click here to ask your question

REFILLING A SEALED HEATING SYSTEM?

I have to remove some radiators from a combie system; takinging them off is fine but what do i need to do to fill the system back up when I replace them? I dont want to damage the boiler or the pump!
Jon, May 2006
turn the boiler off, re-fit the radiators. top the pressure up to 2 bar. go and bleed the rads till the pressure goes completely. then top the boiler up in 1 bar stages until you get water out of all the rads. Hey Presto!

craig, May 2006